Use the MAGLATCH or ELECTROLATCH
spec with the following changes:
Add the designation "-RE"
after the model number
Eliminate the reference to "FailSecure" operation
at the end of the second paragraph. (The exterior shall
always be in a "Fail Secure" mode: key is always
required for entry. Security is maintained in the event
of a power failure).
Insert the following paragraph:
The exterior trim shall operate in a "Fail Safe"
mode. 24vDC power shall be required to maintain the exterior
trim in a locked mode. Loss of power or a release command
from the fire alarms system shall allow entry without key
or release from intercom or card access system.
Add the designation "-RE"
to the POWER SUPPLY UNIT model number.
Add the following sentence to the POWER SUPPLY UNIT specification:The
power supply unit shall contain an input for fire alarm
control panel interruption of power.
|